Terminal functions:
L1 & L2 supply in and out
connections
+R remote indicator
positive connection
(internal 2.2k
resistance to
positive)
–R remote indicator
negative connection
(internal 2.2k
resistance to
negative)
Operating voltage:
17
28V DC
Communication protocol:
Apollo Discovery 5
9V
peak to peak
Quiescent current:
500µA average 750µA peak
Power-up surge current:
1mA
Maximum power-up time:
10s
Alarm current, LED
illuminated:
3.5mA
Remote output
characteristics:
Connects to positive line
through 4.5k(5mA
maximum)
Clean-air analogue value:
23 +4/–0
Alarm level analogue value:
55
Alarm indicator:
2 red Light Emitting Diodes
(LEDs). Optional remote LED
Electro-magnetic
compatibility:
marked
A copy of the relevant
declaration is available on
request
Temperature range:
Max. continuous
operating +60°C
Min. continuous
operating 0° C
Min. operating
20°C
(no condensation/icing)
Storage
30°C to +80°C
Humidity:
0 to 95% relative humidity
(no condensation)
Effect of temperature:
Less than 10% change in
sensitivity over rated range
SAFETY NOTE
In the United Kingdom,
ionisation smoke detectors
are subject to the
requirements of the
Radioactive Substances Act
1960 and to the Ionising
Radiations Regulations
1985 made under the
provisions of the Health and
Safety at Work Act 1974.
The detectors,
independently tested by the
National Radiological
Protection Board (NRPB),
conform to all the
Effect of atmospheric
pressure:
Less than 15% change in
sensitivity up to 2000m
Effect of wind:
Less than 20% change in
sensitivity at speeds up to
10m/s.
Note: slow changes in
ambient conditions will
automatically be compensated
and will not affect sensitivity
Vibration, Impact and
Shock:
To EN54
7:2000
IP rating:
43
Dimensions:
100mm diameter;
42mm height
50mm (height in base)
Weight:
Detector 105g
Detector in base 160g
Materials:
Housing: White
polycarbonate V
0 rated to
UL94
Terminals: Nickel plated
stainless steel
requirements specified in
the ‘Recommendations for
ionisation smoke detectors
in implementation of
radiation standards’
published by the Nuclear
Energy Agency of the
Organisation for Economic
Co-operation and
Development (OECD) 1977.
There is no limit to the
number of ionisation smoke
detectors which may be
installed in any fire
protection system.
Storage regulations depend
on local standards and
legislation, but, in the UK,
up to 500 detectors may be
stored in any premises,
Guidance on storage and
handling can be given by
Apollo Fire Detectors and
full details can be requested
from:
Radioactive Substances
Regulation Function
Environment Agency
Rio House, Waterside Drive
Aztec West, Almondsbury
Bristol BS32 4UD.
Outside the UK, please
contact the relevant
national agency.
TECHNICAL DATA
Discovery Ionisation Smoke
Detector
Part No 58000-500
Specifications are typical at
24V, 23°C and 50% relative
humidity unless otherwise
stated.
Detection principle:
Ionisation chamber
Chamber configuration:
Twin compensating
chambers using one single
sided ionising radiation
source
Radioactive isotope:
Americium 241
Activity:
33.3 kBq, 0.9µCi
Type code:
Bits 2 1 0 4 3 7 6 5
0 1 1 0 0 0 0 0
Supply wiring:
Two-wire supply, polarity
insensitive
although there are
stipulations on storage
facilities if more than 100
ionisation detectors are
stored in one building.
At the end of their
recommended working life
of ten years, ionisation
smoke detectors should be
returned to Apollo for safe
disposal or disposed of in an
otherwise locally approved
and environmentally safe
manner. Please see
"A guide to the care,
maintenance and servicing
of Apollo products",
PP2055.
Vista de pagina 8
1 2 3 4 5 6 7 8 9 10 11 12 13 14 ... 27 28

Comentarios a estos manuales

Sin comentarios