Apollo Smoke Detector XP95 Guía de usuario Pagina 21

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 28
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 20
page
19
Alarm indicator:
Red Light Emitting Diode
(LED)
Type code:
Bits 2 1 0 4 3 7 6 5
1 1 1 1 1 0 0 0
Supply wiring:
Two-wire supply, polarity
insensitive
Loop connections L1/L2:
Flying leads with spade
terminals
Operating voltage:
17
28V DC
Communication protocol:
Apollo Discovery 5
9V
peak to peak
Quiescent current:
350µA average 600µA peak
Power-up surge current:
1mA
Maximum power-up time:
4s
Alarm current, LED
illuminated:
3.35mA
Normal analogue value:
16
Alarm state value:
64
Electro-magnetic
compatibility:
marked
A copy of the relevant
declaration is available on
request
Temperature range:
Max. continuous
operating +60°C
Min. continuous
operating 0°C
Min. operating
20°C
(no condensation/icing)
Storage
30°C to +80°C
Humidity:
0 to 95% relative humidity
(no condensation)
Vibration, Impact and
Shock:
To BS5839: Part 2
IP rating:
53
Dimensions:
87mm x 87mm x 52mm
(surface mount version)
Materials:
Housing: Red self-coloured
PC/ABS
TECHNICAL DATA
Manual Call Point
Specifications are typical
and apply at temperature
23°C and relative humidity
50% unless otherwise
stated.
Call point type:
Break glass
Part No 58000-910
surface mount assembly
Weight 190g
Part No 58000-920
flush mount assembly
Weight 180g
Part No 26729-107
back-box
Part No 26729-110
terminal tray
Call point principle:
Operation of a switch
Vista de pagina 20