page
13
Operating voltage:
17
28V DC
Communication protocol:
Apollo Discovery 5
9V peak
to peak
Quiescent current:
500µA average 750µA peak
Power-up surge current:
1mA
Maximum power-up time:
10s
Alarm current, LED
illuminated:
3.5mA
Remote output
characteristics:
Connects to positive line
through 4.5k(5mA
maximum)
Clean-air analogue value:
23 +4/–0
Alarm level analogue value:
55
Alarm indicator:
2 colourless Light Emitting
Diodes (LEDs); illuminated
red in alarm
Optional remote LED
Electro-magnetic
compatibility:
marked
A copy of the relevant
declaration is available on
request
Temperature range:
Max. continuous
operating +60°C
Min. continuous
operating 0°C
Min. operating
20°C
(no condensation/icing)
Storage
30°C to +80°C
Humidity:
0 to 95% relative humidity
(no condensation)
Effect of temperature on
optical sensor:
Less than 15% change in
sensitivity over rated range.
Slow changes in ambient
conditions will automatically
be compensated and will not
affect sensitivity
Effect of atmospheric
pressure on optical sensor:
None
Effect of wind on optical
sensor:
None
Vibration, Impact and
Shock:
To EN54
7:2000
IP rating:
43
Dimensions:
100mm diameter;
50mm height
58mm (height in base)
Weight:
Detector 105g
Detector in base 160g
Materials:
Housing: White
polycarbonate V
0 rated to
UL94
Terminals: Nickel plated
stainless steel
Smoke element only:
Chamber configuration:
Horizontal optical bench
housing infra-red emitter
and sensor, arranged
radially to detect forward
scattered light
Sensor:
Silicon PIN photo-diode
Emitter:
GaAlAs infra-red light
emitting diode
Sampling frequency:
1 per second
TECHNICAL DATA
Discovery Multisensor
Detector,
Part No 58000-700
Specifications are typical
and apply at temperature
23°C and relative humidity
50% unless otherwise
stated.
Detector principle:
Smoke: Photoelectric
detection of light scattered
by smoke particles
Heat: Temperature-sensitive
resistance
Type code:
Bits 2 1 0 4 3 7 6 5
1 0 1 1 1 0 0 0
Supply wiring:
Two-wire supply, polarity
insensitive
Terminal functions:
L1 & L2 supply in and out
connections
+R remote indicator
positive connection
(internal 2.2k
resistance to positive)
R remote indicator
negative connection
(internal 2.2k
resistance to
negative)
Mode Smoke Sensitivity Temperature Sensitivity Response Type Minimum Time to
(grey smoke) (relative) Alarm (seconds)
% per m % per ft
1 1.1 0.35 High Multisensor 20
2 2.1 0.7 No response to heat Optical 30
3 2.8 0.9 Low Multisensor 20
4 4.2 1.4 High Multisensor 20
5 No response to smoke See text Heat A1 30
Table 4 Multisensor Detector operating modes