
RECEIVING DATA FROM THE IMY
Data is transmitted from the indicator whenever a “T” or “P” command is
received via serial communications or a remote input, E1-CON or optional
E2-CON pin is programmed for print request, is activated. If the abbreviated
transmission was programmed, just data will be transmitted with no built-in
delay. (If full transmission is programmed, then there is a 400 msec min to
800 msec max delay built-in to the string.)
A data string transmission is shown below.
The first two characters transmitted are the unit address number, unless it is
zero, in which case it is left blank. Then two blank spaces are sent. The next
three characters are the abbreviation for the value (mnemonics), which is then
followed by a blank. The actual data is transmitted next. The field is right
justified with leading zeros. Negative numbers are indicated by a minus sign
fixed next to the identifier. A carriage return and a line feed are transmitted
next. For various reasons, “extra” characters are added onto the end of the
above character string. (These characters could be and are used for control or
signaling purposes.) These characters are:
< CR> sent after single line transmissions from IM unit.
< SP>< CR>< LF> sent after “last line of a block” transmission from IM.
For a “T” command or after each “line of a block” transmission, no
additional characters are sent. If the abbreviated transmission is selected, the
address, mnemonics, and any blank spaces (first eight characters) are not
transmitted (the data strings are left justified in this case).
If the transmitted data is overrunning the peripheral’s buffer, the receive
channel to the indicator may be used for handshaking purposes. As a
consequence of this, even if the indicator is to transmit only (ex. to a printer),
current must be flowing in the receive channel to allow transmission.
Examples of transmissions are as follows:
2 INP -125.7F < CR> < LF > full transmission
-125.7 < CR> < LF > abbreviated transmission
CURRENT LOOP INSTALLATION
WIRING CONNECTIONS
When wiring the 20 mA current loop, remove the bottom terminal block
(TBA), located on the rear of the unit. Refer to the numbers listed with the
terminal descriptions below or those located on the label. It is recommended
that shielded (screened) cable be used for serial communications. This unit
meets the EMC specifications using Alpha #2404 cable or equivalent. There
are higher grades of shielded cable, such as four conductor twisted pair, that
offer an even higher degree of noise immunity. Install each wire in its proper
location on the terminal block. When all connections are made, replace the
terminal block into its proper location.
SERIAL TERMINAL DESCRIPTIONS
8. PRINT REQ. - The Print Request terminal is pulled low to activate the unit
to transmit data according to the print function selected in Program Module
#7 (Reference Programming Module #7 for more details). In order for a
print request function to occur, E1-CON (TBA #4) or E2-CON (TBA #8)
must be programmed for print request. Note: In order to guarantee a
print-out, the programmed E-CON pin must be held low for at least 20
msec. If this time exceeds 800 msec, a second print-out may occur.
9. -20 mA SRC. - 20 mA current source return path for the transmit loop.
Current flows into this pin.
10. SI+ (Serial In+) -
11. SI- (Serial In-) -
The unit receives commands on the SI terminals. They are connected in
series with the transmit or output terminals of the device to be connected.
12. SO+/+20 mA SRC. (Serial Out+) - 20 mA current source for the transmit
loop (internally connected).
13. SO- (Serial Out-) -
The unit transmits the requested data on the SO terminals. They are
connected in series to the receive input of the device to be connected.
Note: The Serial Input terminals must be held in the mark condition (current
flowing) in order for the unit to respond to a Print Request terminal activation.
-30-
Comentarios a estos manuales