Apollo Smoke Detector XP95 Manual de usuario Pagina 8

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 11
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 7
Document Ref. XP95app.doc/Rev1 09.06.99 Page 8 of 11 Originator MC Checked by AC
5.7 Apollo XP95 Outstations
The Apollo range of outstations which are compatible with the Puissant panel are as follows:
(i) 55000-832 Mini switch monitor with interrupt. Loop current 0.28mA.
(ii) 55000-819 Output unit provides 1 relay with 1Amp 24V DC contacts - loop
powered. Loop current 4.5mA.
6.0 Loop Isolators
Loop isolators are designed to isolate (or cut out) a section of cable where a short circuit has
been detected. These devices do not require an address setting but are polarity sensitive.
Isolators must be fitted before the 1st device and after the last device on each loop.
6.1 Apollo XP95 Isolating Base
The Apollo XP95 Isolating Base is an XP95 detector base with built-in isolator. Two types
are available:
(i) 45681-320 Isolating Base, permitting a maximum of 10 devices between isolators
(ii) 45681-321 Isolating Base, permitting a maximum of 20 devices between isolators
6.2 Apollo XP95 Isolator
Up to 40 2501/027 XP95 isolators may be fitted to each loop. An isolator termination base is
required. An LED indication is given in the event of a short circuit.
7.0 Loop Powered Sounders
7.1 Control Equipment Loop Powered Sounder
Up to 16 2500/232 loop powered sounders may by used per loop. The sounders will
automatically synchronise (no extra physical connection required) for pulsed alarms.
Please
refer to panel programming guide/disk.
7.1.1 Sound Output
Maximum sound output (loop powered) 90dB at 1m (Loop current 9mA)
Maximum sound output (locally powered) 105dB at 1m
7.1.2 Operation
Channel A operated Continuous sound (evacuate)
Channel B operated Pulsed sound (alert)
Channel C operated Whoop / 2 tone operation (Bomb alert)
-
+
-
+
-
+
-
+
LK
LK
VOLUM
ADDRES
AU
24
LOO
A148 2
Dimensions are 104mm diameter, 85mm high.
Vista de pagina 7
1 2 3 4 5 6 7 8 9 10 11